Configuration Mode (ConF)
S1A28692 03/2010 77
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
FULL [FULL] (continued)
SEt- [SETTINGS]
Inr [Ramp increment]
0.1
T
This parameter is valid for [Acceleration] (ACC), [Deceleration] (dEC), [Acceleration 2] (AC2) and
[Deceleration 2] (dE2). See [Ramp increment] (Inr) page 155
.
0.01
0.1
1
[0,01]: Ramp up to 99.99 seconds
[0,1]: Ramp up to 999.9 seconds
[1]: Ramp up to 6,000 seconds
ACC [Acceleration]
0.00 to 6,000 s (1) 3.0 s
T
Time to accelerate from 0 to the [Rated motor freq.] (FrS) page 74. To have repeatability in ramps, the value of this parameter
must be set according to the possibility of the application. See [Acceleration] (ACC) page 155
.
dEC [Deceleration]
0.00 to 6,000 s (1) 3.0 s
T
Time to decelerate from the [Rated motor freq.] (FrS) page 74 to 0. To have repeatability in ramps, the value of this parameter
must be set according to the possibility of the application. See [Deceleration] (dEC) page 155
.
AC2 [Acceleration 2]
0.00 to 6,000 s (1) 5 s
g
T
Time to accelerate from 0 to the [Rated motor freq.] (FrS) page 74. To have repeatability in ramps, the value of this parameter
must be set according to the possibility of the application. See [Acceleration 2] (AC2) page 156
.
dE2 [Deceleration 2]
0.00 to 6,000 s (1) 5 s
g
T
Time to decelerate from the [Rated motor freq.] (FrS) page 74 to 0. To have repeatability in ramps, the value of this parameter
must be set according to the possibility of the application. See [Deceleration 2] (dE2) page 156
.
tA1 [Begin Acc round]
0 to 100% 10%
g
T
Rounding of start of acceleration ramp as a % of the [Acceleration] (ACC) or [Acceleration 2] (AC2) ramp time. Visible if
[Ramp type] (rPt) is set to [Customized] (CUS). See [Begin Acc round] (tA1) page 155
.
tA2 [End Acc round]
0 to 100% 10%
g
T
Rounding of end of acceleration ramp as a % of the [Acceleration] (ACC) or [Acceleration 2] (AC2) ramp time.
Can be set between 0 and 100% - [Begin Acc round] (tA1).
Visible if [Ramp type] (rPt) is set to [Customized] (CUS). See [End Acc round] (tA2) page 156
.
tA3 [Begin Dec round]
0 to 100% 10%
g
T
Rounding of start of deceleration ramp as a % of the [Deceleration] (dEC) or [Deceleration 2] (dE2) ramp time. Visible if
[Ramp type] (rPt) is set to [Customized] (CUS). See [Begin Dec round] (tA3) page 156
.
tA4 [End Dec round]
0 to 100% 10%
g
T
Rounding of end of deceleration ramp as a % of the [Deceleration] (dEC) or [Deceleration 2] (dE2) ramp time.
Can be set between 0 and 100% - [Begin Dec round] (tA3).
Visible if [Ramp type] (rPt) is set to [Customized] (CUS). See [End Dec round] (tA4) page 156
.
LSP [Low speed]
0 to 599 Hz 0 Hz
T
Motor frequency at minimum reference, can be set between 0 and [High speed] (HSP) page 75. See [Low speed] (LSP)
page 75
.
HSP [High speed]
0 to 599 Hz 50 Hz
T
Motor frequency at maximum reference, can be set between [Low speed] (LSP) and [Max frequency] (tFr). The factory
setting changes to 60 Hz if [Standard mot. freq] (bFr) is set to [60Hz NEMA] (60). See [High speed] (HSP) page 75
.
DRI- > CONF > FULL > SET-