Configuration Mode (ConF)
S1A28692 03/2010 155
Parameters described in this page can be accessed by:
RAMP
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
rPt- [RAMP]
rPt [Ramp type]
[Linear] (LIn)
LIn
S
U
CUS
T
[Linear] (LIn)
[S ramp] (S)
[U ramp] (U)
[Customized] (CUS)
S ramps
The rounding coefficient is fixed,
t1 = 0.6 set ramp time (linear)
t2 = 0.4 set ramp time (round)
t3 = 1.4 set ramp time
The rounding coefficient is fixed,
t1 = 0.5 set ramp time (linear)
t2 = 1.0 set ramp time (round)
t3 = 1.5 set ramp time
tA1: adjustable from 0 to 100%
tA2: adjustable from 0 to (100% - tA1)
tA3: adjustable from 0 to 100%
tA4: adjustable from 0 to (100% - tA3)
t12 = ACC * (tA1(%) / 100 + tA2(%) / 100 + 1)
t34 = DEC * (tA3(%) / 100 + tA4(%) / 100 + 1)
Inr [Ramp increment]
[0,1 ] (0.1)
T
(1)
0.01
0.1
1
This parameter is valid for [Acceleration] (ACC), [Deceleration] (dEC), [Acceleration 2] (AC2) and
[Deceleration 2] (dE2).
[0,01]: Ramp up to 99.99 seconds
[0,1]: Ramp up to 999.9 seconds
[1]: Ramp up to 6,000 seconds
ACC
T
(1)
[Acceleration]
0.00 to 6,000 s (2) 3.0 s
Time to accelerate from 0 to the [Rated motor freq.] (FrS) (page 74). To have repeatability in ramps, the value of this
parameter must be set according to the possibility of the application.
dEC
T
(1)
[Deceleration]
0.00 to 6,000 s (2) 3.0 s
Time to decelerate from the [Rated motor freq.] (FrS) (page 74
) to 0. To have repeatability in ramps, the value of this
parameter must be set according to the possibility of the application.
tA1 [Begin Acc round]
0 to 100% 10%
g
T
(1)
Rounding of start of acceleration ramp as a % of the [Acceleration] (ACC) or [Acceleration 2] (AC2) ramp time.
Can be set between 0 and 100%.
This parameter can be accessed if the [Ramp type] (rPt) is [Customized] (CUS).
FrS
t
0
t2 t2t1
t3
f (Hz)
t2 t2t1
t3
FrS
t
0
f (Hz)
FrS
t
0
t2
t3
f (Hz)
FrS
t
0
f (Hz)
t1 t2
t3
t1
FrS
t
0
tA1 tA2 tA3 tA4
t12
f (Hz)
FrS
t
0
t34
f (Hz)
U ramps
Customized ramps
DRI- > CONF > FULL > FUN- > RPT-