Configuration Mode (ConF)
S1A28692 03/2010 245
Parameters described in this page can be accessed by:
(1) Because, in this case, the detected fault does not trigger a stop, it is recommended to assign a relay or logic output to
its indication.
FLt- [FAULT MANAGEMENT] (continued)
tId- [TORQUE OR I LIM. DETECT]
SSb [Trq/I limit. stop]
[Ignore] (nO)
nO
YES
Stt
LFF
rLS
rMP
FSt
dCI
Behavior in the event of switching to torque or current limitation.
[Ignore] (nO): Detected fault ignored
[Freewheel] (YES): Freewheel stop
[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt) page 158
, without fault tripping. In this case, the
fault relay does not open and the drive is ready to restart as soon as the detected fault disappears, according to the restart
conditions of the active command channel (for example, according to [2/3 wire control] (tCC) and [2 wire type] (tCt) page
112 if control is via the terminals). Configuring an alarm for this detected fault is recommended (assigned to a logic output, for
example) in order to indicate the cause of the stop
[fallback spd] (LFF): Change to fallback speed, maintained as long as the detected fault persists and the run command has
not been removed (1)
[Spd maint.] (rLS): The drive maintains the speed being applied when the detected fault occurred, as long as the detected
fault is present and the run command has not been removed (1)
[Ramp stop] (rMP): Stop on ramp
[Fast stop] (FSt): Fast stop
[DC injection] (dCI): DC injection stop. This type of stop cannot be used with certain other functions. See table on page 150
StO
T
[Trq/I limit. time out]
0 to 9,999 ms 1,000 ms
(If trip has been configured)
Time delay for taking SSF limitation into account.
Code Name / Description Adjustment range Factory setting
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
To change the assignment of this parameter, press the ENT key for 2 s.
2 s
DRI- > CONF > FULL > FLT- > TID-