Configuration Mode (ConF)
140 S1A28692 03/2010
Parameters described in this page can be accessed by:
CCS [Cmd switching]
[ch1 active] (Cd1)
g
This parameter can be accessed if [Profile] (CHCF) is set to [Separate] (SEP) or [I/O profile] (IO).
If the assigned input or bit is at 0, channel [Cmd channel 1] (Cd1) is active.
If the assigned input or bit is at 1, channel [Cmd channel 2] (Cd2) is active.
Cd1
Cd2
LI1
...
[ch1 active] (Cd1): [Cmd channel 1] (Cd1) active (no switching)
[ch2 active] (Cd2): [Cmd channel 2] (Cd2) active (no switching)
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
(not Cd00 to Cd15)
Cd1 [Cmd channel 1]
[Terminals] (tEr)
g
This parameter can be accessed if [Profile] (CHCF) is set to [Separate] (SEP) or [I/O profile] (IO).
tEr
LCC
Mdb
CAn
nEt
[Terminals] (tEr): Terminals
[HMI] (LCC): Graphic display terminal or remote display terminal
[Modbus] (Mdb): Integrated Modbus
[CANopen] (CAn): Integrated CANopen®
[Com. card] (nEt): Communication card (if inserted)
Cd2 [Cmd channel 2]
[Modbus] (Mdb)
g
This parameter can be accessed if [Profile] (CHCF) is set to [Separate] (SEP) or [I/O profile] (IO).
tEr
LCC
Mdb
CAn
nEt
[Terminals] (tEr): Terminals
[HMI] (LCC): Graphic display terminal or remote display terminal
[Modbus] (Mdb): Integrated Modbus
[CANopen] (CAn): Integrated CANopen®
[Com. card] (nEt): Communication card (if inserted)
rFC [Ref. 2 switching]
[Ref.1 channel] (Fr1)
Fr1
Fr2
LI1
...
This parameter can be accessed if [Profile] (CHCF) is set to [Separate] (SEP) or [I/O profile] (IO).
If the assigned input or bit is at 0, channel [Cmd channel 1] (Cd1) is active.
If the assigned input or bit is at 1, channel [Cmd channel 2] (Cd2) is active.
[Ref. 1 channel] (Fr1): [Cmd channel 1] (Cd1) active (no switching)
[Ref. 2 channel] (Fr2): [Cmd channel 2] (Cd2) active (no switching)
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
(not Cd00 to Cd15)
Fr2 [Ref.2 channel]
[No] (nO)
nO
A11
A12
A13
Updt
LCC
Mdb
CAn
nEt
PI
AIU1
0A01
...
OA10
[No] (nO): Not assigned. If [Profile] (CHCF) is set to [Not separ.] (SIM), the command is at the terminals with a zero
reference. If [Profile] (CHCF) is set to [Separate] (SEP) or [I/O profile] (IO), the reference is zero.
[Al1] (A11): Analog input A1
[Al2] (A12): Analog input A2
[Al3] (A13): Analog input A3
[+/-Speed] (UPdt): +/- speed command
[HMI] (LCC): Graphic display terminal or remote display terminal
[Modbus] (Mdb): Integrated Modbus
[CANopen] (CAn): Integrated CANopen®
[Com. card] (nEt): Communication card (if inserted)
[RP] (PI): Pulse input
[AI virtual 1] (AIU1): Virtual analog input 1 with the jog dial
[OA01] (OA01):
Function blocks: Analog Output 01
...
[OA10] (OA10): Function blocks: Analog Output 10
Code Name / Description Adjustment range Factory setting
DRI- > CONF > FULL > CTL-