Configuration Mode (ConF)
S1A28692 03/2010 163
Parameters described in this page can be accessed by:
JOG
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
JOG- [JOG]
Note: This function cannot be used with certain other functions. Follow the instructions on page 148.
JOG [JOG]
[LI3] (LI3)
nO
LI1
...
Pulse operation.
The JOG function is only active if the command channel and the reference channels are on the terminals.
The function is active when the assigned input or bit is at 1.
Example: 2-wire control operation (tCC = 2C).
[No] (nO): Not assigned
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
(not [Cd00] (Cd00) to [Cd15] (Cd15))
JGF [Jog frequency]
0 to 10 Hz 10 Hz
g
T
(1)
Reference in jog operation.
This parameter can be accessed if [JOG] (JOG) is not set to [No] (nO).
1
0
1
0
1
0
0
Ramp
forced to 0.1 s
Reference
JGF reference
JGF reference
LI (JOG)
Forward
Reverse
Ramp
DEC/DE2
Motor
frequency
JGt
DRI- > CONF > FULL > FUN- > JOG-