Configuration Mode (ConF)
S1A28692 03/2010 251
Parameters described in this page can be accessed by:
Process underload detected fault
A process underload is detected when the next event occurs and remains pending for a minimum time
[Unld Time Detect.] (ULt), which is configurable:
The motor is in steady state and the torque is below the set underload limit ([Unld. Thr. 0. Speed.] (LUL),
[Unld. Thr. Nom. Speed.]
(LUn), [Unld. Freq. Thr. Det.] (rMUd) parameters).
The motor is in steady state when the offset between the frequency reference and motor frequency falls
below the configurable threshold [Hysteresis Freq. Att.] (Srb).
Between zero frequency and the rated frequency,
the curve reflects the following equation:
torque = LUL +
The underload function is not active for
frequencies below
[Unld. Freq. Thr. Det.] (rMUd).
A relay or a logic output can be assigned to the signaling of this detected fault in the
[INPUTS / OUTPUTS CFG] (I_O-) menu.
0
LUL
LUn
rMUd
FrS
Frequency
Torque as a % of
the rated torque
Underload
zone
(LUn - LUL) x (frequency)
2
(rated frequency)
2
Code Name / Description Adjustment range Factory setting
FLt- [FAULT MANAGEMENT] (continued)
ULd- [PROCESS UNDERLOAD]
ULt [Unld T. Del. Detect.]
0 to 100 s 0 s
Underload detection time delay.
A value of 0 deactivates the function and makes the other parameters inaccessible.
LUn [Unld. Thr. Nom. Speed.]
20 to 100% 60%
g
T
Underload threshold at rated motor frequency ([Rated motor freq.] (FrS) page 74), as a % of the rated motor torque.
LUL [Unld. Thr. 0. Speed.]
0 to [Unld.Thr.Nom.Speed]
(LUn)
0%
g
T
Underload threshold at zero frequency, as a % of the rated motor torque.
rMUd [Unld. Freq. Thr. Det.]
0 to 599 Hz 0 Hz
g
T
Minimum frequency underload detection threshold.
Srb [Hysteresis Freq. Att.]
0.3 to 599 Hz 0.3 Hz
g
T
Maximum deviation between the frequency reference and the motor frequency, which defines steady state operation.
DRI- > CONF > FULL > FLT- > ULD-