Vue de la page 216
Configuration Mode (ConF)
S1A28692 03/2010 217
MULTIMOTORS / MULTICONFIGURATIONS
Motor or configuration switching [MULTIMOTORS/CONFIG.] (MMC-)
The drive may contain up to 3 configurations, which can be saved using the
[FACTORY SETTINGS] (FCS-) menu, page 69.
Each of these configurations can be activated remotely, enabling adaptation to:
2 or 3 different motors or mechanisms (multimotor mode)
2 or 3 different configurations for a single motor (multiconfiguration mode)
The two switching modes cannot be combined.
Note: The following conditions MUST be observed:
Switching may only take place when stopped (drive locked). If a switching request is sent during operation,
it will not be executed until the next stop.
In the event of motor switching, the following additional conditions apply:
- When the motors are switched, the power and control terminals concerned must also be switched as
appropriate.
- The maximum power of the drive must not be exceeded by any of the motors.
All the configurations to be switched must be set and saved in advance in the same hardware configuration,
this being the definitive configuration (option and communication cards). Failure to follow this instruction can
cause the drive to lock on an [Incorrect config.]
(CFF) state.
Menus and parameters switched in multimotor mode
[SETTINGS] (SEt-)
[MOTOR CONTROL] (drC-)
[INPUTS / OUTPUTS CFG] (I_O-)
[COMMAND] (CtL-)
[APPLICATION FUNCT.] (Fun-) with the exception of the [MULTIMOTORS/CONFIG.] function (to be
configured once only)
[FAULT MANAGEMENT] (FLt)
[MY MENU]
[USER CONFIG.]: The name of the configuration specified by the user in the
[FACTORY SETTINGS] (FCS-) menu
Menus and parameters switched in multiconfiguration mode
As in multimotor mode, except for the motor parameters that are common to the 3 configurations:
Rated current
Thermal current
Rated voltage
Rated frequency
Rated speed
Rated power
IR compensation
Slip compensation
Synchronous motor parameters
Type of thermal protection
Thermal state
The auto-tuning parameters and motor parameters that can be accessed in expert mode
Type of motor control
Note: No other menus or parameters can be switched.