Configuration Mode (ConF)
124 S1A28692 03/2010
Parameters described in this page can be accessed by:
r1H [R1 Holding time]
0 to 9,999 ms 0 ms
The change in state only takes effect once the configured time has elapsed, when the information becomes false.
The holding time cannot be set for the [No drive flt] (FLt) assignment, and remains at 0.
I_O- [INPUTS / OUTPUTS CFG] (continued)
r2- [R2 CONFIGURATION]
r2 [R2 Assignment]
[No] (nO)
bLC
LLC
OCC
EbO
tSY
dCO
OL01
...
OL10
Identical to [R1 Assignment] (r1) page 123
with the addition of:
[Brk control] (bLC): Brake contactor control
[Input cont.] (LLC): Line contactor control
[Output cont] (OCC): Output contactor control
[End reel] (EbO): End of reel (traverse control function)
[Sync. wobble] (tSY): "Counter wobble" synchronization
[DC charging] (dCO): DC bus precharging contactor control
[OL01] (OL01): Function blocks: Logical Output 01
...
[OL10] (OL10): Function blocks: Logical Output 10
r2d
(1)
[R2 Delay time]
0 to 60,000 ms 0 ms
The delay cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [Output cont.] (OCC) and [Input cont.] (LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information becomes true.
r2S [R2 Active at]
[1 ] (POS)
POS
nEG
Configuration of the operating logic:
[1] (POS): State 1 when the information is true
[0] (nEG): State 0 when the information is true
The configuration [1 ] (POS) cannot be modified for the [No drive flt] (FLt), [Brk control] (bLC), [DC charging] (dCO),
and [Input cont.] (LLC) assignments.
r2H [R2 Holding time]
0 to 9,999 ms 0 ms
The holding time cannot be set for the [No drive flt] (FLt), [Brk control] (bLC) and [Input cont] (LLC) assignments, and
remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information becomes false.
I_O- [INPUTS / OUTPUTS CFG] (continued)
LO1- [LO1 CONFIGURATION]
LO1 [LO1 assignment]
[No] (nO)
bLC
LLC
OCC
EbO
tSY
dCO
OL01
...
OL10
Identical to [R1 Assignment] (r1) page 123
with the addition of (shown for information only as these selections can only be
configured in the [APPLICATION FUNCT.] (FUn-)) menu:
[Brk control] (bLC): Brake contactor control
[Input cont.] (LLC): Line contactor control
[Output cont] (OCC): Output contactor control
[End reel] (EbO): End of reel(traverse control function)
[Sync. wobble] (tSY): "Counter wobble" synchronization
[DC charging] (dCO): DC bus precharging contactor control
[OL01] (OL01): Function blocks: Logical Output 01
...
[OL10] (OL10): Function blocks: Logical Output 10
LO1d [LO1 delay time]
0 to 60,000 ms (1) 0 ms
The delay cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [Output cont.] (OCC) and [Input cont.] (LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information becomes true.
LO1S [LO1 active at]
[1 ] (POS)
POS
nEG
Configuration of the operating logic:
[1] (POS): State 1 when the information is true
[0] (nEG): State 0 when the information is true
The configuration [1 ] (POS) cannot be modified for the [No drive flt] (FLt), [Brk control] (bLC) and [Input cont.] (LLC)
assignments.
Code Name / Description Adjustment range Factory setting
DRI- > CONF > FULL > I_O- > R1-