Configuration Mode (ConF)
160 S1A28692 03/2010
Parameters described in this page can be accessed by:
(1) The parameter can also be accessed in the [SETTINGS] (SEt-) menu.
(2) In corresponds to the rated drive current indicated in the Installation manual and on the drive nameplate.
(3) These settings are independent of the [AUTO DC INJECTION] (AdC-) function.
IdC2 [DC inject. level 2]
0.1 In (2) to [DC inject. level 1]
(IdC)
0.5 In (2)
g
T
(1) (3)
CAUTION
RISK OF DAMAGE TO THE MOTOR
Check that the motor will withstand this current without overheating.
Failure to follow these instructions can result in equipment damage.
Injection current activated by logic input or selected as stop mode, once period of time [DC injection time 1] (tdI) has
elapsed.
This parameter can be accessed if [Type of stop] (Stt) is set to [DC injection] (dCI) or if [DC injection assign.] (dCI)
is not set to [No] (nO).
tdC [DC injection time 2]
0.1 to 30 s 0.5 s
g
T
(1) (3)
CAUTION
RISK OF DAMAGE TO THE MOTOR
• Long periods of DC injection braking can cause overheating and damage the motor.
• Protect the motor by avoiding long periods of DC injection braking.
Failure to follow these instructions can result in equipment damage.
Maximum injection time [DC inject. level 2] (IdC2) for injection, selected as stop mode only.
This parameter can be accessed if [Stop type] (Stt) is set to [DC injection] (dCI).
dOtd [Dis. operat opt code]
[Ramp stop] (rMp)
nSt
rMp
Disable operation stop mode.
[Freewheel] (nSt): Disable drive function
[Ramp stop] (rMp): Ramp stop then disable drive function
Code Name / Description Adjustment range Factory setting
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
DRI- > CONF > FULL > FUN- > STT-