Password (COd)
282 S1A28692 03/2010
The drive has 2 access codes, enabling 2 access levels to be set up:
- PIN code 1 is a public unlock code: 6969.
- PIN code 2 is an unlock code known only to Schneider Electric Product Support. It can only be
accessed in [Expert] (EPr) mode.
- Only one PIN1 or PIN2 code can be used, the other must remain set to [OFF] (OFF).
Note: When the unlock code is entered, the user access code appears.
The following items are access-protected:
Return to factory settings ([FACTORY SETTINGS] (FCS-) menu.
The channels and parameters protected by the [MY MENU] (MYMn-) as well as the menu itself.
The custom display settings ([3.4 DISPLAY CONFIG.] (dCF-) menu).
Code Name / Description Adjustment range Factory setting
COd- [5 PASSWORD]
CSt [State]
[Unlocked] (ULC)
LC
ULC
Information parameter, cannot be modified.
[Locked] (LC): The drive is locked by a password
[Unlocked] (ULC): The drive is not locked by a password
COd [PIN code 1]
[OFF] (OFF) to 9,999 [OFF] (OFF)
1st access code. The value [OFF] (OFF) indicates that no password has been set [Unlocked] (ULC). The value [ON] (On)
indicates that the drive is protected and an access code must be entered in order to unlock it. Once the correct code has been
entered, it remains on the display and the drive is unlocked until the next time the power supply is disconnected.
PIN code 1 is a public unlock code: 6969.
COd2 [PIN code 2]
[OFF] (OFF) to 9,999 [OFF] (OFF)
This parameter can only be accessed in [Expert] (EPr) mode.
2nd access code. The value [OFF] (OFF) indicates that no password has been set [Unlocked] (ULC). The value [ON] (On)
indicates that the drive is protected and an access code must be entered in order to unlock it. Once the correct code has been
entered, it remains on the display and the drive is unlocked until the next time the power supply is disconnected.
PIN code 2 is an unlock code known only to Schneider Electric Product Support.
When [PIN code 2] (COd2) is not set to [OFF] (OFF), the [1.2 MONITORING] (MOn-) menu is the only one visible. Then if
[PIN code 2] (COd2) is set to [OFF] (OFF) (drive unlocked), all menus are visible.
If the display settings are modified in [3.4 DISPLAY CONFIG.] (dCF-) menu, and if [PIN code 2] (COd2) is not set to
[OFF] (OFF), the visibility configured is kept. Then if [PIN code 2] (COd2) is set to OFF (drive unlocked), the visibility
configured in [3.4 DISPLAY CONFIG.] (dCF-) menu is kept.
ULr [Upload rights]
[Permitted] (ULr0)
ULr0
ULr1
Reads or copies the current configuration to the drive.
[Permitted] (ULr0): The current drive configuration can be uploaded to the graphic display terminal or PC Software.
[Not allowed] (ULr1): The current drive configuration can only be uploaded to the graphic display terminal or PC Sofware if
the drive is not protected by an access code or if the correct code has been entered.
dLr [Download rights]
[Unlock. drv] (dLr1)
dLr0
dLr1
dLr2
dLr3
Writes the current configuration to the drive or downloads a configuration to the drive.
[Locked drv] (dLr0): A configuration file can only be downloaded to the drive if the drive is protected by an access code,
which is the same as the access code for the configuration to be downloaded.
[Unlock. drv] (dLr1): A configuration file can be downloaded to the drive or a configuration in the drive can be modified if the
drive is unlocked (access code entered) or is not protected by an access code.
[Not allowed] (dLr2): Download not authorized.
[Lock/unlock] (dLr3): Combination of [Locked drv.] (dLr0) and [Unlock. drv] (dLr1).