Configuration Mode (ConF)
122 S1A28692 03/2010
Parameters described in this page can be accessed by:
I_O- [INPUTS / OUTPUTS CFG] (continued)
AU2- [VIRTUAL AI2]
AU2A [AIV2 assignment]
Possible assignments for [AI virtual 2] (AIU2): Virtual analog input 2 via communication channel, to be configured with [AI2
net. channel] (AIC2).
Identical to [AIV1 assignment] (AU1A) page 121
.
AIC2 [AI2 net. Channel]
[No] (nO)
g
[VIRTUAL AI2] (AU2A) source channel.
This parameter can also be accessed in the [PID REGULATOR] (
PId-) submenu page 196.
Scale: The value 8192 transmitted by this input is equivalent to 10 V on a 10 V input.
nO
Mdb
CAn
nEt
[No] (nO): Not assigned
[Modbus] (Mdb): Integrated Modbus
[CANopen] (CAn): Integrated CANopen®
[Com. card] (nEt): Communication card (if inserted)
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
Code Name / Description Adjustment range Factory setting
DRI- > CONF > FULL > I_O- > AU2-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com