Configuration Mode (ConF)
S1A28692 03/2010 257
Parameters described in this page can be accessed by:
nMA8 [Scan. IN8 address]
0
Address of the 8th input word.
COM- [COMMUNICATION] (continued)
OCS- [COM. SCANNER OUTPUT]
[Scan. Puy address] (nCA1) to [Scan. Out4 address] (nCA4) could be used for Fast Task of the communication scanner
(see Modbus & CANopen® communication manual).
nCA1 [Scan.Out1 address]
8,501
Address of the 1st output word.
nCA2 [Scan.Out2 address]
8,602
Address of the 2nd output word.
nCA3 [Scan.Out3 address]
0
Address of the 3rd output word.
nCA4 [Scan.Out4 address]
0
Address of the 4th output word.
nCA5 [Scan.Out5 address]
0
Address of the 5th output word.
nCA6 [Scan.Out6 address]
0
Address of the 6th output word.
nCA7 [Scan.Out7 address]
0
Address of the 7th output word.
nCA8 [Scan.Out8 address]
0
Address of the 8th output word.
COM- [COMMUNICATION] (continued)
Md1- [MODBUS NETWORK]
Add [Modbus Address]
[OFF] (OFF) to 247 [OFF] (OFF)
OFF
-
[OFF] (OFF)
1 to 247
AMOC [Modbus add Com. C.]
[OFF] (OFF) to 247 [OFF] (OFF)
g
OFF
-
[OFF] (OFF)
1 to 247
tbr [Modbus baud rate]
[19.2 Kbps] (19 2)
4 8 - 9 6 - 19 2 - 38 4 kbps on the integrated display terminal.
4800, 9600, 19200 or 38400 bauds on the graphic display terminal.
tFO [Modbus format]
[8-E-1] (8E1)
8O1 - 8E1 - 8n1, 8n2
ttO [Modbus time out]
0.1 to 30 s 10.0 s
0.1 to 30 s
COM1 [Mdb com stat]
r0t0
r0t1
r1t0
r1t1
[r0t0] (r0t0): Modbus no reception, no transmission = communication idle
[r0t1] (r0t1): Modbus no reception, transmission
[r1t0] (r1t0): Modbus reception, no transmission
[r1t1] (r1t1): Modbus reception and transmission
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
Code Name / Description Adjustment range Factory setting
DRI- > CONF > FULL > COM- > ICS-