Configuration Mode (ConF)
142 S1A28692 03/2010
Parameters described in this page can be accessed by:
As the graphic display terminal may be selected as the command and/or reference channel, its action modes
can be configured.
The parameters on this page can only be accessed on the graphic display terminal, and not on the integrated
display terminal.
Comments:
The display terminal command/reference is only active if the command and/or reference channels from the
terminal are active with the exception of [T/K] (Ft) (command via the display terminal), which takes
priority over these channels. Press [T/K] (Ft) (command via the display terminal) again to revert control
to the selected channel.
Command and reference via the display terminal are impossible if the latter is connected to more than one
drive.
The JOG, preset speed and +/- speed functions can only be accessed if [Profile] (CHCF) is set to
[Not separ.] (SIM).
The preset PID reference functions can only be accessed if [Profile] (CHCF) is set to
[Not separ.] (SIM) or [Separate] (SEP).
The [T/K] (Ft) (command via the display terminal) can be accessed regardless of the [Profile] (CHCF).
Code Name / Description Adjustment range Factory setting
Fn1 [F1 key assignment]
[No] (nO)
nO
FJOG
FPS1
FPS2
FPr1
FPr2
FuSP
FdSP
Ft
[No] (nO): Not assigned
[Jog] (FJOG): JOG operation
[Preset spd2] (FPS1): Press the key to run the drive at the 2nd preset speed [Preset speed 2] (SP2) page 84
. Press STOP
to stop the drive.
[Preset spd3] (FPS2): Press the key to run the drive at the 3rd preset speed [Preset speed 3] (SP3) page 84
. Press STOP
to stop the drive.
[PID ref. 2] (FPr1): Sets a PID reference equal to the 2nd preset PID reference [Preset ref. PID 2] (rP2) page 86
, without
sending a run command. Only operates if [Ref.1 channel] (Fr1) is set to [HMI] (LCC). Does not operate with the [T/K] (Ft)
function.
[PID ref. 3] (FPr2): Sets a PID reference equal to the 3rd preset PID reference [Preset ref. PID 3] (rP3) page 87
, without
sending a run command. Only operates if [Ref.1 channel] (Fr1) is set to [HMI] (LCC). Does not operate with the [T/K] (Ft)
function.
[+speed] (FUSP): Faster, only operates if [Ref.2 channel] (Fr2) is set to [HMI] (LCC). Press the key to run the drive and
increase the speed. Press STOP to stop the drive.
[- speed] (FdSP): Slower, only operates if [Ref.2 channel] (Fr2) is set to [HMI] (LCC) and if a different key has been
assigned to [+ speed]. Press the key to run the drive and decrease the speed. Press STOP to stop the drive.
[T/K] (Ft): Command via the display terminal: Takes priority over [Cmd switching] (CCS) and over
[Ref. 2 switching] (rFC ).
Fn2 [F2 key assignment]
[No] (nO)
Identical to [F1 key assignment] (Fn 1) page 142.
Fn3 [F3 key assignment]
[No] (nO)
Identical to [F1 key assignment] (Fn 1) page 142.
Fn4 [F4 key assignment]
[No] (nO)
Identical to [F1 key assignment] (Fn 1) page 142.
bMp [HMI cmd.]
[Stop] (StOP)
g
When the [T/K] (Ft) function is assigned to a key and that function is active, this parameter defines the behavior at the moment
when control returns to the graphic display terminal or remote display terminal.
StOp
bUMF
[Stop] (StOP): Stops the drive (although the controlled direction of operation and reference of the previous channel are copied
(to be taken into account on the next RUN command)).
[Bumpless] (bUMF): Does not stop the drive (the controlled direction of operation and the reference of the previous channel
are copied)
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.