Schneider Electric Magelis XBT GT Spécifications Page 178

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 246
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 177
178 35010372 10/2010
Power Plug Illustration
1 - Power plug for XBT GT1000/1005/2000/4000 series and XBT GK2000 series
2 - Power plug for XBT GT5000/6000/7000 series and XBT GK5000 series
How to connect the Power Cord
The following table explains how to connect the power plug:
NOTE:
z Do not solder the wire directly to the power receptable pin.
z The power supply cord should meet the specification shown above. Be sure to
twist the power cords together, up to the power plug, for EMC cancellation. (See
illustration as shown below)
Connection Wire
+ 24 V
-0 V
FG Grounded terminal connected to the unit chassis.
Step Action
1 Remove the power cord from the power supply.
2 Remove the power plug from unit.
3 Remove 7 mm (.28 in.) of the vinyl cover of each of the power cord’s wires.
4 If using stranded wire, twist the ends. Tinning the ends with solder reduces risk
of fraying and ensures good electrical transfer.
5 Connect the wires to the power plug by using flat-blade screwdriver (Size
0.6 X 3.5)
6 Torque the mounting screws: 0.5 to 0.6 nm (5 to 7 lb-in)
7 Replace the power plug to the power connector.
Vue de la page 177
1 2 ... 173 174 175 176 177 178 179 180 181 182 183 ... 245 246

Commentaires sur ces manuels

Pas de commentaire