35010372 10/2010 111
Terminal Configuration Switches
Introduction
The RS485 line polarization selector switch is available on all XBT GT and XBT GK
series.
The CF card DIP switches are available on:
z XBT GT2000 series
z XBT GT4000 series
z XBT GT5000 series
z XBT GT6000 series
z XBT GT7000 series
z XBT GK series
z XBT GH series
Parameters of RS485 Line Polarization Selector Switch
The following table explains the RS485 line polarization selector switch parameters:
Function ON OFF Comment
Controls the
polarization
of the RS485
serial line.
RS485 serial line is
polarized (620 Ω pull-
up on D1 and 620 Ω
pull-down on D0).
No internal
polarization.
Polarization requires activation (ON)
when the following two conditions are
met:
z Modbus or Unitelway protocol is
implemented
z No other equipment is polarizing
the bus