EtherNet/IP Features
S1A28701 03/2010 55
Cyclical Exchanges (Implicit Exchanges)
Overview
This part gives a description of the 3 assembly sets and how to configure them.
Principle of Control configuration
By the configuration of the control, it is possible to decide from what channel the drive receives its commands
and setpoint, either permanently or depending on a switching command. Numerous configurations are
possible. For more information, refer to the Programming manual and Communication parameters manual.
The following configurations are some of the available possibilities.
The selection of the assembly set is made with the EtherNet/IP communication adapter.
Control With Communication Scanner
If the default assemblies (100, 101) are selected, the Altivar 32 will be controlled according to its native profile
CiA402.-IEC-61800-7 (See “CiA®402 - IEC61800-7 Functional Profile” on page 72). By configuring the
communication scanner, it is possible to assign any relevant parameter of the drive to the 6 input and 6 output
variables of the assemblies.
The size of the assembly (100, 101) is fixed and is equal to 6 words.
The mapping of the other parameters is made with the communication scanner.
The configuration of the addresses defined with (OCA x) and (OMA x) can be made with the graphic keypad:
For assembly 100: [COMMUNICATION] (COM-) menu, [COMMUNICATION CARD] (Cbd-)
submenu.
For assembly 101: [COMMUNICATION] (COM-) menu, [COMMUNICATION CARD] (Cbd-)
submenu.
See menu [1.2 MONITORING] (MOn-) > COMMUNICATION MAP to monitor the communication scanner.
Altivar
The mapping of the 100-101 assemblies is
made with the communication scanner
(OCA1)(OMA1)
(OCA2)(OMA2)
(OCA3)(OMA3)
(OCA4)(OMA4)
(OCA5)(OMA5)
(OCA6)(OMA6)
Assembly
100
Assembly
101
Up to additional
parameters are
mapped
This configuration can be made with:
HMI
Keypad
SoMove
Webserver
EtherNet/IP option
EtherNet/IP
scanner
100-101
Native drive profile
CiA402
Vue de la page 54