Controlling an ATV32 From Modbus TCP (M340)
S1A28701 03/2010 47
Configuration of the VW3 A3 616 Communication Card
Conf > Full > Communication > Communication card
Configuration of the Command
In the Command Menu [Command] (CtL):
[Ref1 Channel] (Fr1): is set according to the communication source you can choose in the following
table:
[Rv Inhibition] (rIn): default.
[Stop Key priority] (PSt): default.
[Profile] (CHCF): defines if the drives operates in combined mode (reference and command from the
same channel)
For the current example, [Profile] (CHCF) will be adjusted to [Combined] (SIM) as reference and control
are originated from the communication network:
ETHM = MBTP Defines the protocol used: Modbus TCP
IPM = MANU IP address is defined locally
IP card = 10.0.0.11 -
IP Mask 255.0.0.0 -
IP Master = 10.0.0.10 Defines the address of the I/O scanner client
(M340 Ethernet module)
OCA1 8501 > CMD In the example we will use the default
parameters + an additional parameter for
monitoring
OCA2 8602 > LFRD
OCA3 -
OCA4 -
OCA5 -
OCA6 -
OMA1 3201 > ETA
OMA2 8604 > RFRD
OMA3 3207 > ULN
OMA4 -
OMA5 -
OMA6 -
Origin of the control Ref1 Channel setting
Modbus TCP [Com. card] (nEt)
Profile Ref1 Channel setting
CiA402 [Combined] (SIM)
Separate [Separate] (SEp)
I/O Profile [I/O Mode] (IO)