Xantrex XW Solar Charge Controller Installation
4–4 975-0239-01-01
This manual for use by qualified personnel only
Choosing a Location
The Xantrex XW Solar Charge Controller is designed to be mounted vertically to
the side or the top of the power distribution panel.
The Xantrex XW SCC must be installed indoors in a dry, protected location away
from flammable materials, sources of high temperature, moisture, and vibration,
and direct sunlight. The location must also be sheltered from direct sunlight, rain,
snow, and wind-blown debris.
If using “sealed” batteries, the controller can be mounted in the same enclosure
as long as it is adequately ventilated.
For optimal and safe operation, ensure there is adequate clearance around the
Xantrex XW SCC. See Table 4-2. If clearances are reduced below these
minimums, rated performance may not be achieved.
CAUTION: Equipment Damage
Never install the Xantrex XW SCC where it is exposed to salt water spray.
Exposure to salt water will void the warranty and may cause a malfunction or a
shock hazard.
WARNING: Explosion/Corrosion Hazard
To reduce the risk of fire or explosion, do not install the Xantrex XW SCC in sealed
compartments containing batteries or in locations that require ignition-protected
equipment.
To reduce the risk of corrosion from hydrogen-sulfide gas vented by batteries, do
not install the Xantrex XW SCC in sealed compartments containing batteries.
Table 4-2 Minimum Clearance Requirements
Location Minimum Clearance
Above 6 inches (150 mm). When units are mounted to the side of the
power distribution panel in a vertical stack, the topmost unit must
maintain the minimum clearance to the nearest surface.
In front Sufficient room to allow for easy access to read the display, to
prevent accidental contact with the heat sink, and to perform
maintenance.
On sides 6 inches (150 mm) on at least one side of the overall assembly.
A maximum of two units can be mounted side by side or side
mounted against the power distribution panel. In both
configurations, the minimum clearance around the outermost unit
must be maintained.