The Xantrex XW Automatic Generator Start
975-0239-01-01 5–9
This manual for use by qualified personnel only
Preparing an Installation
Before installing the Xantrex XW Automatic Generator Start Module, consider
how and where the unit will be mounted. Pre-plan the connection routes between
the Xantrex XW Automatic Generator Start, the generator, thermostats, and the
Xantrex XW Automatic Generator Start. Refer to the Xantrex XW AGS Owner’s
Guide for additional information.
See Chapter 3, “Xantrex Xanbus Network Installation”, for more information about
installing a Xantrex Xanbus-enabled device as part of a network-managed
power system.
Materials and Tools Required
The following tools and materials may be needed to install the Xantrex XW
Automatic Generator Start:
Mounting template (supplied)
Wiring harness (manufacturer part number 809-0917, supplied)
Four #6 screws, 1¼ inch (supplied)
#16 or #18 AWG wire (see “Wire Size and Length” on page 5–13)
Schneider Electric network cables or equivalent (Category 5)
Network terminators (if required)
Phillips screwdriver
Wire cutters and wire strippers
Choosing a Location
The Xantrex XW Automatic Generator Start should be installed in a location that
meets the following requirements:
Dry
The unit is intended for use in a dry location. The Xantrex XW
Automatic Generator Start
complies with UL458 Marine
Supplement drip-test requirements, but the location should be as
dry as possible.
Cool
The Xantrex XW Automatic Generator Start
operates between
-4 and 122 °F (-20 and 50 °C).
Safe
The Xantrex XW Automatic Generator Start
is not ignition
protected. Do not install it in areas requiring ignition-protected
equipment, such as compartments housing gasoline engines.
Close to
generator
Avoid excessive wire lengths and use the recommended wire
lengths and sizes (see “Wire Size and Length” on page 5–13).
It is more important for the Xantrex XW Automatic Generator Start
to be close to the generator than close to the inverter, although
for safety reasons, the Xantrex XW Automatic Generator Start
should not be installed in the same compartment as a
gasoline-powered generator.