Step 4: Wiring the Inverter
975-0239-01-01 2–17
This manual for use by qualified personnel only
Figure 2-10 Battery Temperature Sensor (RJ11) Port Location and Installation
Battery Temperature Sensor
Battery Temperature
Sensor Port (RJ11)
1
RJ11 jack
If using the adhesive backing,
install the Battery Temperature
Sensor on the side of the battery
below the electrolyte level.
Note: If other Xantrex Xanbus connected components supply a BTS
or are BTS enabled, it is not necessary to install all of them at once.
Only one BTS needs to be installed.
However, if multiple battery-strings are being used to form a battery
bank, multiple sensors can be installed. In this case, the system will
use the highest temperature from all the inputs as its operational
parameter.