5—I/O Menu 06/2003
78
High Speed Attained (FLA)
The logic output is at state 1 if the motor frequency is equal to the
high speed value (HSP).
Current Threshold Attained (CtA)
The logic output is at state 1 if the motor current meets or exceeds
the current threshold set by the Ctd parameter in the 2—Adjust menu.
Frequency Reference Attained (SrA)
The logic output is at state 1 if the motor frequency is equal to the
speed reference value.
Motor Thermal State Attained (tSA)
The logic output is at state 1 if the motor thermal state meets or
exceeds the thermal threshold set by the ttd parameter in the
2—Adjust menu.
Brake Logic Command (bLC) (This parameter is only assignable to R2)
Brake Logic Command allows management of a mechanical brake by
the drive controller. Figure 19 shows a timing diagram for Brake
Logic.