Page 1 - Keypad Display VW3A58101

Altivar® 58 TRXAdjustable Speed Drive ControllersKeypad Display VW3A58101Instruction BulletinRetain for future use.

Page 2

© 1998–2003 Schneider Electric All Rights ReservedChapter 1—Overview VVDED397047USR6/03Firmware Revision Information 06/2003103Q 2000 V3.1 IE 16 V3.0

Page 3 - TABLE OF CONTENTS

© 1998–2003 Schneider Electric All Rights ReservedChapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03Procedure 1: Bus Voltage Measurement 06/

Page 4 - Table of Contents 06/2003

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 3—Diagnostics and Troubleshooting06/2003 Procedure 2: Checking Supply Vol

Page 5 - 06/2003 Table of Contents

© 1998–2003 Schneider Electric All Rights ReservedChapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03Procedure 3: Checking the Peripheral Equ

Page 6

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 3—Diagnostics and Troubleshooting06/2003 Fault Codes and Messages103Fault

Page 7 - 06/2003 Introduction

© 1998–2003 Schneider Electric All Rights ReservedChapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03Fault Codes and Messages 06/2003104ERR 3

Page 8

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 3—Diagnostics and Troubleshooting06/2003 Fault Codes and Messages105Ini A

Page 9

© 1998–2003 Schneider Electric All Rights ReservedChapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03Fault Codes and Messages 06/2003106OtF M

Page 10

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 3—Diagnostics and Troubleshooting06/2003 Fault Codes and Messages107Table

Page 11 - • Local command

© 1998–2003 Schneider Electric All Rights ReservedChapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03Fault Codes and Messages 06/2003108

Page 12 - Retaining Screw

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Appendix A—Drive Controller Confi

Page 13 - 06/2003 Keypad Display

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 1—Overview06/2003 Keypad Display11Keypad DisplayThe keypad display allows

Page 14 - 50/60 Hz switch

© 1998–2003 Schneider Electric All Rights ReservedAltivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Appendix A—Drive Controller Configuration

Page 15

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Appendix A—Drive Controller Confi

Page 16

© 1998–2003 Schneider Electric All Rights ReservedAltivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Appendix A—Drive Controller Configuration

Page 17

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Appendix A—Drive Controller Confi

Page 18

© 1998–2003 Schneider Electric All Rights ReservedAltivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Appendix A—Drive Controller Configuration

Page 19 - 06/2003 Access Levels

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Appendix A—Drive Controller Confi

Page 20 - Figure 6: Menus

© 1998–2003 Schneider Electric All Rights ReservedAltivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Appendix A—Drive Controller Configuration

Page 21

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Appendix B—Options and Accessorie

Page 22 - Access Levels 06/2003

© 1998–2003 Schneider Electric All Rights ReservedAltivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Appendix B—Options and Accessories 06/200

Page 23 - 06/2003 Language Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Appendix B—Options and Accessorie

Page 24

© 1998–2003 Schneider Electric All Rights ReservedChapter 1—Overview VVDED397047USR6/03Keypad Display 06/200312MountingTo mount the keypad display, fi

Page 25 - Validate? ENT/ESC

© 1998–2003 Schneider Electric All Rights ReservedAltivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Appendix B—Options and Accessories 06/200

Page 26 - CUS:Customize

VVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Index© 1998–2003 Schneider Electric All Rights Reserved121INDEX Symbols+SP 59+speed

Page 27 - 1-DISPLAY MENU

© 1998–2003 Schneider Electric All Rights Reserved122Altivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Index 06/2003FCL 87Fdb 46FFt 33FLA 61,

Page 28 - 1—Display Menu

VVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Index© 1998–2003 Schneider Electric All Rights Reserved123NnAr 86nCr 43nLd 46NO 59,

Page 29 - 2—Adjust Menu

© 1998–2003 Schneider Electric All Rights Reserved124Altivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Index 06/2003STR 90–91Str 56, 63, 67St

Page 31

91598106011107Altivar® 58 TRX Keypad Display VW3A58101Instruction Bulletin Schneider Electric8001 Highway 64 EastKnightdale, NC 27545 USA1-888-Squar

Page 32

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 1—Overview06/2003 Keypad Display13for mounting the keypad display on the

Page 33

© 1998–2003 Schneider Electric All Rights ReservedChapter 1—Overview VVDED397047USR6/03Keypad Display 06/200314Figure 3: Location of 50/60 Hz Switch50

Page 34

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 1—Overview06/2003 Keypad Display15Function of Keys and Meaning of Display

Page 35 - Handling Macro-Configuration

© 1998–2003 Schneider Electric All Rights ReservedChapter 1—Overview VVDED397047USR6/03Keypad Display 06/200316Quick Configuration First prepare your

Page 36

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 1—Overview06/2003 Keypad Display179. Configure the fault management param

Page 37 - Use Macro-Configuration

© 1998–2003 Schneider Electric All Rights ReservedChapter 1—Overview VVDED397047USR6/03Access Levels 06/200318Access LevelsThe position of the access

Page 38

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 1—Overview06/2003 Access Levels19Total Unlock Position – All modes: this

Page 39 - Reassignment

See page 17 for the Minimum Start-Up Procedure. DANGERHAZARDOUS VOLTAGE• Read and understand this bulletin in its entirety before installing or opera

Page 40 - Reassignment (continued)

© 1998–2003 Schneider Electric All Rights ReservedChapter 1—Overview VVDED397047USR6/03Access Levels 06/200320Figure 6: MenusLanguageLnGMacro-ConfigCF

Page 41 - 3—Drive Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 1—Overview06/2003 Access Levels21Principles of ProgrammingThe principle o

Page 42 - 3—Drive Menu 06/2003

© 1998–2003 Schneider Electric All Rights ReservedChapter 1—Overview VVDED397047USR6/03Access Levels 06/200322

Page 43

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 Language Menu23CHAPTER 2—MENUSThis chapter explains menus

Page 44 - Set the CoS parameter to the

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/03Macro-Configuration Menu 06/200324Table 3: Drive Controller I/O As

Page 45

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 Macro-Configuration Menu25Transferring a file created for

Page 46

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/03Drive Controller Identification Screen 06/200326Customizing the Ma

Page 47

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 Drive Controller Identification Screen27Increasing the Pow

Page 48 - T1 = 1/Dec

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/031—Display Menu 06/2003281—Display MenuDisplay parameters can be vi

Page 49

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 2—Adjust Menu292—Adjust MenuThe Adjust menu is accessible

Page 50

VVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Table of Contents© 1998–2003 Schneider Electric All Rights Reserved3TABLE OF CONTEN

Page 51

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/032—Adjust Menu 06/200330There are two types of adjustment parameter

Page 52 - 4—Control Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 2—Adjust Menu31Inv. Phases ACb Electronic output phase in

Page 53 - LIx: Reverse

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/032—Adjust Menu 06/200332Stability - % StA Frequency loop stability

Page 54

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 2—Adjust Menu33NOTE: DC Inj. Time is only available if aut

Page 55 - Parameter

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/032—Adjust Menu 06/200334Jump Freq.3- Hz JF3 Third skip frequency:

Page 56

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 2—Adjust Menu35Additional Adjustment Parameters for Materi

Page 57

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/032—Adjust Menu 06/200336Preset Sp.4- Hz ★ SP4 Fourth preset speed

Page 58 - 5—I/O Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 2—Adjust Menu37Additional Adjustment Parameters for Genera

Page 59

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/032—Adjust Menu 06/200338Additional Adjustment Parameters for Variab

Page 60

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 2—Adjust Menu39Additional Adjustment Parameters After I/O

Page 61

© 1998–2003 Schneider Electric All Rights Reserved4Altivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Table of Contents 06/2003Reference Switc

Page 62

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/032—Adjust Menu 06/200340BrReleasTime -s [4]brt Brake release time

Page 63

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 3—Drive Menu413—Drive MenuThis menu is accessible when the

Page 64 - 5—I/O Menu 06/2003

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/033—Drive Menu 06/200342Optimal performance is obtained:• By ensurin

Page 65 - 06/2003 5—I/O Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 3—Drive Menu43Table 11: 3—Drive Menu ParametersParameter C

Page 66

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/033—Drive Menu 06/200344Mot.CosPhi CoS Motor CosPhi, motor power fa

Page 67 - LI1 LI2 LI3 LI4 +24 AIX

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 3—Drive Menu45Auto Tuning tUn Initiates an autotune when

Page 68

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/033—Drive Menu 06/200346Energy Eco nLd Optimizes the motor efficien

Page 69

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 3—Drive Menu47Type of stop Stt Type of stop:STN–FSTNST–DC

Page 70

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/033—Drive Menu 06/200348Ramp Type rPt Defines the type of accelerat

Page 71 - —Drive menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 3—Drive Menu49Trq.Limit1 -% [4]tLI Torque limit allows lim

Page 72 - • Nominal motor current

VVDED397047USR6/03 Altivar® 58 TRX Keypad Display VW3A5810106/2003 Table of Contents© 1998–2003 Schneider Electric All Rights Reserved56—Fault Menu

Page 73

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/033—Drive Menu 06/200350Sw Freq -kHz SFr Selection of switching fre

Page 74

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 3—Drive Menu51 PG Type ★ PGt Defines the type of sensor us

Page 75 - Input Code Range Description

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/034—Control Menu 06/2003524—Control MenuThe Control Menu is accessib

Page 76

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 4—Control Menu53Table 13: 4—Control Menu: 2-Wire Control T

Page 77 - • If AI3 = 10 V: limit = TLI

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/034—Control Menu 06/200354deadb./pedst bSP This function can be use

Page 78

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 4—Control Menu55Table 14: 4—Control Menu: Other Parameters

Page 79 - T = non-adjustable delay

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/034—Control Menu 06/200356Save Ref Str This function allows saving

Page 80

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 4—Control Menu57Stop Priorit. PSt This function gives pri

Page 81 - • Brake engage time (bEt):

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/2003585—I/O MenuThis menu allows you to assign funct

Page 82

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu59Table 15 shows which functions can be assigned

Page 83

© 1998–2003 Schneider Electric All Rights Reserved6Altivar® 58 TRX Keypad Display VW3A58101 VVDED397047USR6/03Table of Contents 06/2003

Page 84

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200360ATN: Autotune Auto-tuning XPIF: PI regulator

Page 85 - 6—Fault Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu61Table 16 shows which functions can be assigned

Page 86 - Table 21: 6—Fault Menu

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200362After the I/O have been assigned, additional p

Page 87

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu63R2, LO TAD Drive thermal threshold attained dt

Page 88

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200364Figure 12: Function Compatibility Chart➞➞➞➞➞➞➞

Page 89 - 7—Files Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu65Using the Logic InputsRun Forward and Run Reve

Page 90 - Table 22: 7—File Menu

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200366Ramp SwitchingThis function allows switching b

Page 91 - 06/2003 7—Files Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu67and the -Speed input decreases the speed. If l

Page 92 - Factory

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200368Figures 15 and 16 show a wiring example and a

Page 93 - Password Fault

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu69Preset Speeds2, 4, or 8 speeds can be preset,

Page 94 - 8—Application Menu

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 1—Overview06/2003 Introduction7CHAPTER 1—OVERVIEWIntroductionThe Altivar

Page 95 - Red FAULT LED

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200370Reference Switching (Auto/Manual)Switching bet

Page 96 - Maintenance

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu71Fast StopFast stop is a braked stop with the d

Page 97 - Precautions

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200372parameters are automatically scaled by the com

Page 98

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu73External FaultAssigning a logic input to Exter

Page 99

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200374Using the Analog InputsThe AI1 input is set fo

Page 100 - Do not use

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu75Table 20 provides a description of the inputs

Page 101

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200376Assignment of AI2 and AI3Summing Speed Referen

Page 102

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu77Total resistance of the probe circuit at 20 °C

Page 103 - Fault Codes and Messages

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200378High Speed Attained (FLA)The logic output is a

Page 104

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu79Parameters accessible in the 2—Adjust menu whe

Page 105

© 1998–2003 Schneider Electric All Rights ReservedChapter 1—Overview VVDED397047USR6/03Introduction 06/20038communication protocols are supported by c

Page 106 - ≥ 200 ms)

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200380Recommendations for configuring the Brake Logi

Page 107 - Trip Point Reset Point

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu81• Acceleration/deceleration time:It is advisab

Page 108

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200382maximum values (AOL and AOH parameters) are co

Page 109 - VVDED397047USR6/03 Altivar

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 5—I/O Menu83maximum configured value of the analog output

Page 110

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/035—I/O Menu 06/200384PI ErrorWhen configured for PI error, OPE, the

Page 111

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 6—Fault Menu856—Fault MenuThis menu is only accessible whe

Page 112 - Table 35: Menu 7—File Menu

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/036—Fault Menu 06/200386Nb max reset nAr This parameter is used to

Page 113 - (continued

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 6—Fault Menu87OutPhaseLoss OPL Use to enable the output p

Page 114 - (continued)

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/036—Fault Menu 06/200388LossFollower LFL Allows activation of a los

Page 115 - Menu 7 – FILES Menu (page 86)

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 7—Files Menu897—Files MenuThe Files menu is accessible whe

Page 116

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 1—Overview06/2003 Firmware Revision Information9Firmware Revision Informa

Page 117 - Catalog No. Description

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/037—Files Menu 06/200390Table 22: 7—File MenuParameter Code Descript

Page 118

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 7—Files Menu91Reinitializing the Drive ControllerFigure 21

Page 119

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/037—Files Menu 06/200392• If storing a file, the display automatical

Page 120

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 2—Menus06/2003 7—Files Menu93NOTE: Menu access allowed by the locking swi

Page 121

© 1998–2003 Schneider Electric All Rights ReservedChapter 2—Menus VVDED397047USR6/038—Communication Menu 06/200394functionality of the drive controlle

Page 122

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 3—Diagnostics and Troubleshooting06/2003 Keypad Display and Indicating LE

Page 123

© 1998–2003 Schneider Electric All Rights ReservedChapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03Using Fault Codes and Messages to Solve

Page 124

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 3—Diagnostics and Troubleshooting06/2003 Precautions97At regular interval

Page 125

© 1998–2003 Schneider Electric All Rights ReservedChapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03Procedure 1: Bus Voltage Measurement 06/

Page 126 - 91598106011107

© 1998–2003 Schneider Electric All Rights ReservedVVDED397047USR6/03 Chapter 3—Diagnostics and Troubleshooting06/2003 Procedure 1: Bus Voltage Measure