CIP Objects
76
S1A28702 05/2010
Connection Object
Class Code
Class Attributes
Attributes of Instance 1 - Explicit Message Instance
Refer to DeviceNet specification for more information.
Hexadecimal Decimal
16#05 5
Attribute ID Access Name Need Data type Value Details
1 Get Revision Opt. UINT 1 -
2 Get Max instances Opt. UINT 4 5 defined
instances
Attribute
ID
Access Name Need Data type Value Details
1 Get State Req. USINT - 0: Non-existent
3: Established
5: Deferred Delete
2 Get Instance_type Req. USINT 0 Explicit Message
3 Get TransportClass_trigger Req. BYTE 16#83 Class 3 server
4 Get Produced_connection_id Req. UINT 10xxxxxx011 xxxxxx = Node address
5 Get Consumed_connection_id Req. UINT 10xxxxxx100 xxxxxx = Node address
6 Get Initial_comm_characteristics Req. BYTE 16#21 Explicit messaging via Group
2
7 Get Produced_connection_size Req. UINT 36 Produced data maximum
size
(in bytes)
8 Get Consumed_connection_size Req. UINT 36 Consumed data maximum
size (in bytes)
9 Get/Set Expected_packet_rate Req. UINT 2500 2.5 sec. (TimeOut)
12 Get/Set Watchdog_timeout_action Req. USINT 1 or 3 1: Auto-Delete
3: Deferred Delete (Default)
13 Get Produced connection path
length
Req. UINT 0 Length of attribute 14 data
14 Get Produced connection path Req. Array of
UINT
Null Empty
15 Get Consumed connection path
length
Req. UINT 0 Length of attribute 16 data
16 Get Consumed connection path Req. Array of
UINT
Null Empty