Advanced Configuration Features
122
31004624 8/2009
The three digital output modules utilize one Modbus register apiece for data. The
analog output module requires two registers, one for each output channel. A total of
five registers (registers 40001 through 40005) are used for this configuration:
1 The value represented in register 40004 is in the range +10 to -10 V, with 11-bit resolution
plus a sign bit in bit 15.
2 The value represented in register 40005 is in the range +10 to -10 V, with 11-bit resolution
plus a sign bit in bit 15.
The digital modules use the LSBs to hold and display their output data. The analog
module uses the MSBs to hold and display its output data.