Planning Instruction 66571758GB0 49/2011 Fire Detection
FX 3NET + SLC FIRE ALARM SYSTEM
Part 1: General Rules
These are the planning instructions for an FX 3NET fire detection and alarm system
consisting of
- FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET control panels
- SLC compatible intelligent field devices
In this document FX refers to all FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET panels. For
information specifically related to a specific panel model, that model type is indicated.
We reserve the right to make technical changes without notice.
The planning instructions consist of 3 parts:
- Part 1: General Rules 6657 1758GBx
- Part 2: System Devices 6657 1759GBx
- Part 3: Additional Information 6657 1760GBx
See also the following instructions:
- User guide of the WinFX3Net Configuration Tool 6657 1782GBx
- FX3Net Configuration Data 6657 1783GBx
- FX3Net System Capacity Calculation Tool 6657 1746GBx
Note!
Instructions given by local authorities must be followed when planning the system.
Vue de la page 0
1 2 3 4 5 6 ... 63 64

Résumé du contenu

Page 1 - Part 1: General Rules

Planning Instruction 66571758GB0 49/2011 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 1: General Rules T

Page 2

Planning Instruction 66571758GB0 Fire Detection 10 3. FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET construction The FX panel is a modular construct

Page 3

Planning Instruction 66571758GB0 Fire Detection 11 3.2 FXL 3NET cabinet The FXL cabinet has space for the following - 1 x UI2 - 1 x MC2 - 1

Page 4 - End user

Planning Instruction 66571758GB0 Fire Detection 12 3.5 FX battery cabinet The FX battery cabinet has space for the following - 4 x battery 12

Page 5

Planning Instruction 66571758GB0 Fire Detection 13 4. Mechanical installation 4.1 Installation, FX 3NET and FXL 3NET control panels Schneider

Page 6

Planning Instruction 66571758GB0 Fire Detection 14 4.2 Installation, FXM 3NET control panel Schneider Electric Pelco Finland Oy Kalkkipellon

Page 7

Planning Instruction 66571758GB0 Fire Detection 15 4.3 Installation, FXS 3NET control panel Schneider Electric Pelco Finland Oy Kalkkipellon

Page 8 - DAPXFMPX REPX

Planning Instruction 66571758GB0 Fire Detection 16 5. FX 3NET, multi-panel networked system FX 3NET is the solution for fire detection systems

Page 9

Planning Instruction 66571758GB0 Fire Detection 17 Example 2 Consider an industrial site with two large buildings and a gate building. The gate s

Page 10 - MC2 OP

Planning Instruction 66571758GB0 Fire Detection 18 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Page 11

Planning Instruction 66571758GB0 Fire Detection 19 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Page 12

Planning Instruction 66571758GB0 Fire Detection 2 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 13

Planning Instruction 66571758GB0 Fire Detection 20 6. Addressable detection circuits, addresses, zones 6.1 FX-SLC addressable detection circui

Page 14

Planning Instruction 66571758GB0 Fire Detection 21 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Page 15

Planning Instruction 66571758GB0 Fire Detection 22 Closed detection circuit (highly recommended) A closed detection circuit gives the highest saf

Page 16 - Panel 1 Panel 2 Panel 3

Planning Instruction 66571758GB0 Fire Detection 23 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Page 17

Planning Instruction 66571758GB0 Fire Detection 24 6.4.1 Control groups for all event types (Ctrl A and Ctrl B) Control group A and B inputs a

Page 18

Planning Instruction 66571758GB0 Fire Detection 25 Sequence example 2: reset during delay Input (e.g. MCP in alarm state)Fire alarm deviceFire a

Page 19

Planning Instruction 66571758GB0 Fire Detection 26 6.4.4 Control group use for delayed alarm Control groups A and B can be used together with

Page 20

Planning Instruction 66571758GB0 Fire Detection 27 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Page 21

Planning Instruction 66571758GB0 Fire Detection 28 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Page 22

Planning Instruction 66571758GB0 Fire Detection 29 EOL resistor, Exi 4k7, 5%, not Exi 2k94, 1%, not Exi 4k7, 5%, Exi 2k94, 1%, Exi Max cable

Page 23

Planning Instruction 66571758GB0 Fire Detection 3 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 24

Planning Instruction 66571758GB0 Fire Detection 30 8. Cabling 8.1 Cables of addressable detection circuit x10x10x10C CC1472058369147205836914

Page 25

Planning Instruction 66571758GB0 Fire Detection 31 8.2 Cables of conventional detection circuits CLC, alarm device lines, input/output lines

Page 26 - Fire detection

Planning Instruction 66571758GB0 Fire Detection 32 8.3 Cables of serial communication lines and power supply FXSFMPXDAPXREPXMCOXFX_12181818181

Page 27

Planning Instruction 66571758GB0 Fire Detection 33 8.4 Grounding of communication cables FX y serial adapterFX x serial adapterGND TR- TR+SYS

Page 28

Planning Instruction 66571758GB0 Fire Detection 34 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Page 29

Planning Instruction 66571758GB0 Fire Detection 35 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Page 30

Planning Instruction 66571759GB0 49/2012 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 2: System Devices

Page 31

Planning Instruction 66571759GB0 Fire Detection 2 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 32

Planning Instruction 66571759GB0 Fire Detection 3 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 33

Planning Instruction 66571759GB0 Fire Detection 4 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 34

Planning Instruction 66571758GB0 Fire Detection 4 1.3 Regulations EN54-14 “Guidelines for Planning, Installation, Commissioning and Maintenance

Page 35

Planning Instruction 66571759GB0 Fire Detection 5 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 36 - Part 2: System Devices

Planning Instruction 66571759GB0 Fire Detection 6 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 37

Planning Instruction 66571759GB0 Fire Detection 7 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 38

Planning Instruction 66571759GB0 Fire Detection 8 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 39

Planning Instruction 66571760GB0 49/2011 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 3: Additional Information

Page 40

Planning Instruction 66571760GB0 Fire Detection 2 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 41

Planning Instruction 66571760GB0 Fire Detection 3 1. Examples of FX 3NET system structure 1.1 System structure examples Example 1 S1S1S1 S1

Page 42

Planning Instruction 66571760GB0 Fire Detection 4 Example 3: FX 3NET communication segments, long distances CCCCCCCCCCCCMMMMMMMMMMMMFX_FX_FX_FX_

Page 43

Planning Instruction 66571760GB0 Fire Detection 5 Example 4: Factory area  FX_FX_FX_ FX_FX _FX_ FX_FX_S1S1S1S1S1S1S2S2S2MLMLMLMLMLMLMLMLMLMLS2S

Page 44

Planning Instruction 66571760GB0 Fire Detection 6 1.2 Cable length of a segment FX_ FX_FX_Max. 1000 m abcFX_FX_FX_FX_a + b+ c = maks. 1000

Page 45

Planning Instruction 66571758GB0 Fire Detection 5 1.4 Example of a site plan for the FX 3NET fire detection system 008016015001 002 003 004 005

Page 46

Planning Instruction 66571760GB0 Fire Detection 7 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 47 - Max. 5 km *)

Planning Instruction 66571760GB0 Fire Detection 8 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 48

Planning Instruction 66571760GB0 Fire Detection 9 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 49 - Max. 1000 m

Planning Instruction 66571760GB0 Fire Detection 10 4. FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET connections, settings and fuses 4.1 FX 3NET and

Page 50

Planning Instruction 66571760GB0 Fire Detection 11 4.2 FXM 3NET panel external connections Schneider Electric Pelco Finland Oy Kalkkipellon

Page 51

Planning Instruction 66571760GB0 Fire Detection 12 4.3 FXS 3NET panel external connections Schneider Electric Pelco Finland Oy Kalkkipellon

Page 52

Planning Instruction 66571760GB0 Fire Detection 13 4.4 Connectors on the MC2 board Terminal name Connector symbol Purpose Description 24 V -

Page 53

Planning Instruction 66571760GB0 Fire Detection 14 4.5 Connectors on the PS board Terminal name Connector symbol Purpose Description 30 VAC

Page 54

Planning Instruction 66571760GB0 Fire Detection 15 4.7 Connectors on each CLC board Terminal name Connector symbol Purpose Description - Conve

Page 55

Planning Instruction 66571760GB0 Fire Detection 16 4.9 Connectors on each IOC board Terminal name Connector symbol Purpose Description Alarm

Page 56

Planning Instruction 66571758GB0 Fire Detection 6 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 57

Planning Instruction 66571760GB0 Fire Detection 17 4.10 FX 3NET, FXL 3NET and FXM 3NET Fuses The 30VAC input from the transformer is protected

Page 58

Planning Instruction 66571760GB0 Fire Detection 18 4.11 FX 3NET, FXL 3NET and FXM 3NET Battery backup The FXM cabinet has space for 2 x 12 Ah /

Page 59

Planning Instruction 66571760GB0 Fire Detection 19 5. FX Settings and configuration 5.1 Settings in the FX panel Settings on the FX-MC2 board

Page 60

Planning Instruction 66571760GB0 Fire Detection 20 Settings on the FX-CLC board With settings on the FX-CLC board, the following can be set and

Page 61

Planning Instruction 66571760GB0 Fire Detection 21 Settings on the FX-IOC board With settings on the FX-IOC board, the following can be set and

Page 62

Planning Instruction 66571758GB0 Fire Detection 7 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Page 63 - + 16

Planning Instruction 66571758GB0 Fire Detection 8 2.5 FX 3NET stand-alone system diagram Schneider Electric Pelco Finland Oy Kalkkipellont

Page 64

Planning Instruction 66571758GB0 Fire Detection 9 2.6 Networked FX 3NET system diagram Schneider Electric Pelco Finland Oy Kalkkipellontie 6

Commentaires sur ces manuels

Pas de commentaire