Vue de la page 20
Communications Adapter Register Mapping
17
Width: 178 mm
Height: 216 mm
20
2.2.2 Data Register Mapping for Analog I/O bases
Data in controller registers is mapped to the field terminals of analog I/O bases in
the following way:
H Each analog value is mapped to one word.
H The Most Significant Word (MSW) is sent or received first.
H The words sent by the communications adapter to the I/O base represent the
output values and parameters (Outputwords).
H The words sent from the I/O base to the communications adapter represent
the input values and status (Inputwords).
Data mapping for one analog I/O base is shown as an example:
Figure 4 I/O Mapping of the 170 AAI 140 00 (16 Input Channels) e.g.
Input Data from 170 AAI 140 00
MSW = Word 16
Word 15
Word 5
Value channel 16
Value channel 15
Value channel 5
Word 4
Word 3
Word 2
LSW = Word 1
Value channel 4
Value channel 3
Value channel 2
Value channel 1
Output Data to 170 AAI 140 00
MSW = Word 16
Word 15
Word 5
empty
empty
empty
Word 4
Word 3
Word 2
LSW = Word 1
Parameters, Channels 5 ... 8
Parameters, Channels 1 .. 4
Parameters, Channels 13 ... 16
Parameters, Channels 9 ... 12
to to
Additional documentation: Refer to the I/O bases User Manual (870 USE 002