Schneider Electric INTERBUS Basic Manuel d'utilisateur Page 16

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 15
Interbus with TSX Momentum Overview
20
12
1.4 Configuration Limits
Table 1 Interbus Configuration Limits for Standard PLC (e.g. TSX Quantum)
Parameters
Limitations
max. number of nodes (slaves) 256
max. distance between 2 nodes Twisted pair, shielded = 400 m (1 200 ft)
max. distance between 2 nodes Fiber optic (HCS) = 300 m (900 ft)
max. distance between 2 nodes fiber optic cable, polymer fiber = 50 m (150 ft)
max. length of network 13 km (8 mi)
max. number of I/O points 4096
Transfer Rate 500 kBits/s
Data throughput for 1 000 I/O points ~ 4 ms
Vue de la page 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 35 36

Commentaires sur ces manuels

Pas de commentaire