PowerLogic™ PM5300 series user guide Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved68
Setting Up 1-Second Alarms (continued)
NOTE: The Over Demand alarms are applicable for systems in which the energy is
delivered to the customer only.
17. Press
to select Priority, then
press Edit.
18. Press + and - to scroll through
priority options None, High,
Medium, or Low.
NOTE: See “Alarm Priorities”
on page 66 for more
information.
19. Press OK to set the priority.
20. Press
to select Select
Digital Output, then press Edit.
21. Press + and - to scroll through
the list of digital outputs to
associate with the alarm.
22. Press OK to select a digital
output to be associated with the
selected alarm.
23. If the selected digital output
already has an association that
will be lost by making the new
selection, a confirmation screen
appears.
Press Yes to accept the
changes and return to the
previous screen.
Press No to keep the
existing configuration in use
and return to the previous
screen.
24. Press
to save all alarm
selections and return to the
previous screen.
25. Press to save all 1-second
alarm selections.