Schneider Electric Multi-Loader Spécifications Page 27

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 40
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 26
1
2
3
4
5
6
7
8
9
10
25
Combinations for
customer assembly
(continued)
Altivar
®
12
variable speed drives
Motor starters: Three-phase supply voltage
200 to 240 V
Motor starters (continued)
Standard
power
ratings of
three-phase
4-pole
50/60 Hz Hz
motors
(2)
Variable speed
drive
Combination with control circuit
(circuit-breaker + contactor)
Minimum conguration
(circuit-breaker only)
TeSys
contactor
(1)
TeSys
®
motor
circuit-breaker
(3)
Operating
range or
rating
Maximum
short-circuit
current Icu
Modular
circuit-breaker
(4)
kW HP A kA
M1 A1 Q1 KM1
Three-phase supply voltage: 200 to 240 V 50/60 Hz
0.18 0.25 ATV12H018M3 GV2ME07 1.6 to 2.5 > 100 LC1K09
GV2L07 2.5 > 100
4-pole C60N 6 10
0.37 0.55 ATV12p037M3 GV2ME08 2.5 to 4 > 100 LC1K09
GV2L08 4 > 100
4-pole C60N 6 10
0.75 1 ATV12p075M3 GV2ME14 6 to 10 > 100 LC1K09
GV2L14 10 > 100
4-pole C60N 10 10
1.5 2 ATV12pU15M3 GV2ME16 9 to 14 > 100 LC1K12
GV2L16 14 > 100
4-pole C60N 16 10
2.2 3 ATV12pU22M3 GV2ME20 13 to 18 > 100 LC1D18
GV2L20 18 > 100
4-pole C60N 20 10
3 ATV12pU30M3 GV2ME21 17 to 23 50 LC1D25
GV2L22 25 50
4-pole C60N 20 10
4 5 ATV12pU40M3 GV2ME32 24 to 32 50 LC1D25
GV2L22 25 50
4-pole C60N 32 10
Combinations of C60N circuit-breakers/Vigi C60 add-on modules
C60N
2-pole/4-pole
Vigi C60
Rating (A) Rating (A) Type (5) Sensitivity
6 25 A “si” 30 mA
10 25 A “si” 30 mA
16 25 A “si” 30 mA
20 25 A “si” 30 mA
32 40 A “si” 30 mA
Recommendations for special uses:
All RH10/RH21/RH99/RHU residual current protection devices with separate sensors are
compatible as long as the type and sensitivity of the add-on modules given in the table above are
observed.
It is advisable to connect one RCD (residual current device) per drive. In this case, a type B RCD
must not be located downstream of a type A or AC RCD.
(1) For a complete list of references for TeSys contactors, please refer to the "Motor starter
solutions - Control and protection components" and "Motor starters up to 150 A" catalogs or visit
"www.schneider-electric.us".
(2) Motor power indicated for combination with an ATV12Hppppp drive with the same rating.
For combination with an ATV12Pppppp drive, refer to the specic manual for the Altivar
®
12
base plate version, available on our website at “www.schneider-electric.us”.
(3) TeSys motor circuit-breakers:
- GV2MEpp: Thermal magnetic motor circuit-breakers with pushbutton control
- GV2Lpp: Magnetic motor circuit-breakers with control by rotary knob
(4) 4-pole C60N modular circuit-breaker
(5) For additional protection against direct contact, with a three-phase power supply and access
to the DC bus terminals (PA/+ and PC /-), the add-on module must be type B with a sensitivity of
30 mA.
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22
2
4
1
6
5
3
W/T3
U/T1
V/T2
R/L1
S/L2
T/L3
U1
W1
V1
M1
3
2
4
1
3
6
5
2
4
1
3
6
5
Motor starter with three-phase power supply
Q1:
C60N4P
KM1:
TeSys LC1pppp
(if control circuit)
A1:
ATV12ppppM3
Q1:
GV2pppp
M1:
200..240 V three-phase
asynchronous motor
or
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Vue de la page 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 39 40

Commentaires sur ces manuels

Pas de commentaire