PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 2 Quick Start Guide
© 2010 Schneider Electric. All rights reserved.
23
Clear INTG and MD
The power meters are equipped with energy integrator INTG, where the
energy parameters are accumulated
INTG CLR: Clear both INTG and MD values
INTG MD: Clear only MD values (where MD is maximum demand)
NOTE: means blinking
y means blinking y
INTG Clear
1. From RMS, press . The display shows CLR.
CODE entry is required to clear the INTG values.
2. Press for two seconds. The display shows CODE 2000 with blinking
2. The factory set CODE is 1000.
3. Press . The display shows CODE 1000 with blinking 1.
4. Press once or four times to accept the new value.
After the successful CODE entry, the display shows CLR INTG.
5. In order to clear INTG, press . The display shows CLR INTG y with
blinking y.
6. Press to clear INTG. The display flashes PASS and then CLR
INTG.
7. Press . The display shows CLR.
8. Press to return to RMS page.
NOTE: If you do not want to clear the integrators, press to change the value from CLR
INTG y to CLR INTG n in step 5. Then press . The display flashes FAIL and shows CLR
INTG. Proceed to step 7.