MBX Driver Help
Cyberlogic Technologies Inc. - 37 -
Proceed to Configuring Peer Cop Communications to continue.
Configuring Peer Cop Communications
1. Select the
Peer Cop
tab.
2. If you will not use Peer Cop communication, clear the
Enable Peer Cop
check box,
click
Close,
and then proceed directly to Configuring the MBX Gateway Server.
If you will use Peer Cop communication, check the
Enable Peer Cop
check box and
continue with this section.
3. Click the
Global Inputs
button.
The Global Input Configuration window will open.
Note
Up to 32 words of global input data may be requested from each Modbus Plus node
configured here, with the limitation that the total amount of requested data must not
exceed 500 words.