Configuring the Programmable Models
890 USE 103 00
67
4.8 Indicator Codes During Downloading
# % " "!""# !  "! !
" " ! #!"!%!'!"!""#!  !
" '#"! !%# 
4.8.1 Normal Download Codes
 ! # % 
Indication Meaning
Port 4 –– Flashing two times per second Ready for downloading
Port 3 –– ON intermittently Receiving download from host
Port 2 –– ON (combined with port 3) Writing to BM85 RAM
Port 1 –– ON (combined with port 3) Erasing BM85 RAM
4.8.2 Error Codes
  # !# % "#! !"&"
#""!'!  "" "!# " !
  ""  #!"%"! "%&"!
 !""" !!%!"'""  !""
# ""'!%!""  !%""
% ""##!!"" !" " ""$'
 "!"!"!""
Indicators Pattern Hexadecimal Digit
4 – 3 – 2 – 1 Steady Upper digit
4 – 3 – 2 – 1 Flashing Lower digit
Error Code
(Hexadecimal) Meaning
F1 BM85 kernel is reloading
F4 Program or task returned to BM85 bootstrap
F8 Program or task called abort()
FD Could not extend heap – program called malloc() or equivalent
and had insufficient memory
FE Could not create heap – not enough memory below code area
FF Not enough memory to copy program to RAM area