Bulletin No. VVDED397044US R12/00 Section 1—Installation & Configuration
December 2000 Hardware Setup
© 1998–2000 Schneider Electric All Rights Reserved
19
Figure 12: Terminal Locations (Product Frame Size 7)
Cable Routing Practices
When wiring the ATV58 drive controllers to a MODBUS PLUS network,
follow all wiring practices required by national and local electrical codes.
Observe the following guidelines:
Avoid areas of high temperature, moisture, vibration, or other
mechanical stress.
Secure the cable where necessary to prevent its weight and the weight
of other cables from pulling or twisting the cable.
Use cable ducts, raceways, or other structures to protect the cable.
Use these structures for signal wiring paths. They should not contain
power wiring.
Control Terminals
Power Terminals
Ground Terminal