Catalog
CAT WMC-4
1 Catalog WMC-4
Water-Cooled Oil-Free Chiller
With Magnetic Bearing Compressors
Model WMC 145S – 290D
125 to 290 Tons, 440 to 970 kW
3/60/460, 3/50/400
R-134a
Vue de la page 0
1 2 3 4 5 6 ... 55 56

Résumé du contenu

Page 1 - Model WMC 145S – 290D

Catalog CAT WMC-4 1 Catalog WMC-4 Water-Cooled Oil-Free Chiller With Magnetic Bearing Compressors Model WMC 145S – 290D 125 to 290 Tons, 440 to 9

Page 2 - MICROTECH II

MicroTech II Control Features and Benefits FEATURE BENEFIT Easy integration into Building Management System via McQuay’s exclusive Open Choice™ com

Page 3 - TABLE OF CONTENTS

The MicroTech II controller's memory retains a record of faults and the time/date stamp. The controller's memory (no batteries required) can

Page 4 - Environmental Responsibility

MicroTech II Controller Increases Chiller Operating Economy Many standard features have been incorporated into MicroTech II control in order to maint

Page 5 - Exceptional Control

13 Catalog WMC-4 Communication Capabilities Versatile Communications Capabilities Give You Even More Control Building Automation Systems All Micro

Page 6 - Reduced Installation Costs

Table 1, Typical Data Point Availability Typical Data Points1 (W = Write, R = Read) Capacity Limit Output R Cond EWT R Evap Water Pump Status R

Page 7 - Benefit Summary

15 Catalog WMC-4 Unit Design Features • No increase in operating cost due to displacement of heat transfer surface by non-condensables Variable Fr

Page 8 - Control Features

the U.S. Department of Transportation for refrigerant shipping containers, as well as ASME vessel codes. When service is required, the refrigerant cha

Page 9 - 9 Catalog WMC-4

Part Load Efficiency Chillers usually spend 99% of their operating hours under part load conditions and most of this time at less than 60% of design c

Page 10 - 10 Catalog WMC-4

The ARI Standard 550/590-98 for Centrifugal or Screw Water-Chilling Packages and associated manuals define certification and testing procedures and pe

Page 11 - Changing Setpoints

19 Catalog WMC-4 Chiller Identification WMC centrifugal chillers are selected by computer and identified by their components on the selection print

Page 12 - Chiller Operating Economy

Cutaway View of Magnetic Bearing Compressor, Nominal 75 Tons Compressor Major Running Gear Components MICROTECH II® Controller, Operator Interf

Page 13 - Communication Capabilities

Pressure Drop Curves NOTE: The -B and -C designations shown on the curves refer to vessel tube count, which is determined by the computer selection pr

Page 14 - Network Protocol Options

Figure 12, 2-Pass Evaporators WMC Evap - Water Side Pressure Drop(2 pass)01020304050600 200 400 600 800 1000 1200EGPM - gpmE2212-BE

Page 15 - Unit Design Features

Figure 14, 3-Pass Evaporators WMC Evap - Water Side Pressure Drop(3 pass)01020304050607080900 200 400 600 800EGPM - gpmEPD - ftE2212-CE2212-DE2209-C

Page 16 - 16 Catalog WMC-4

23 Catalog WMC-4 Sound Data The following sound pressure ratings are for measurements one meter from the unit and in accordance with ARI Standard

Page 17 - ARI Certification

Dimensions Figure 16, WMC 145S (NOTE: See page 28 for notes.) 145S DRAWING NOT YET AVAILABLE 24 C

Page 18 - 18 Catalog WMC-4

Figure 17, WMC 150D, 2-Pass Evaporator, 2-Pass Condenser See page for notes.) 28330654401_2 Pass Evap Production Unit“B”20.4(518.2)42.7(1084.6)9.1

Page 19 - Chiller Identification

Figure 18 WM C 250D, 2-Pass Evaporator, 2-Pass Condenser for notes.) (NOTE: See page 28 26 Catalog WMC-4

Page 20 - Pressure Drop Curves

Figure 19, WMC 290D, 2-Pass Evaporator, 2- Pass Condenser (NOTE: See page for notes.) 28 35146.93732.28136.43465.5811.2284.2311.1282.5817.1434.981

Page 21 - (2 pass)

Drawing Notes 1. All dimensions are in Inches and [Millimeters] unless noted otherwise. 2. Manufacturing Tolerances, final connections to unit must a

Page 22 - (3 pass)

Figure 20, Mounting/Lifting Weights LB RB Shipping Weight, lbs (kg) Lifting Location inch (mm) WMC Model Vessel Models (Size) LF RF LB R

Page 23 - Sound Data

TABLE OF CONTENTS WMC 145D, 150D Dual Compressor... 34 THE NEW COMPRESSOR TECHNOLOGY...4 Single Point Connection...

Page 24 - Dimensions

Marine Water Box Dimensions with Victaulic or Flanged Connections Marine water boxes are an available option on all evaporator and condenser sizes. Ep

Page 25 - Connections

Physical Data and Weights Evaporator Refrigerant-side design pressure is 200 psi (1380 kPa). Water-side is 150 psi (1034 kPa). Approximate total squ

Page 26 - (NOTE: See page

Relief Valves Vessel Relief Valves Relief valve connection sizes are 1 inch FPT and are in the quantity shown in Table 9. Relief Valve Piping Sizes T

Page 27

33 Catalog WMC-4 Electrical Data Wiring, fuse and wire size must be in accordance with the National Electric Code (NEC). Figure 22, Terminal Box,

Page 28 - Drawing Notes

General Note: The RLA for use in the following tables is obtained by the selection of a specific unit by McQuay. When shipped, a unit will bear the sp

Page 29 - Circuit #1

Single-point Connection, Optional Table 14, WMC 145D, 150D Electrical Data Field Wire RLA Minimum Circuit LRA Max Fuse Size (Per Compressor) Ampacity

Page 30 - REAR FACING ONLY

Single Point Connection, Optional Field Wire RLA Minimum Circuit LRA Max Fuse Size (Per Compressor) Ampacity (MCA) Quantity Wire GA 72 to 76 Amps 110

Page 31 - Physical Data and Weights

80* CHILLED WATER PUMP STARTERSEWI-2CP2CP1NOTE 11NOTE 11NOTE 11*NOTE 8NOTE 8NOTE 9HOA C4* COOLING TOWER FIRST STAGE STARTER* COOLING TOWER

Page 32 - Relief Valves

38 Catalog WMC-4 Power Factor The full load power factor exceeds 0.90 for all capacity selections. VFD Line Harmonics Despite their many benefits,

Page 33 - Electrical Data

The power line noise emissions associated with variable frequency and variable speed drives can cause disturbances in nearby equipment. Typical distur

Page 34 - WMC 145S, Single Compressor

The New Compressor Technology Next Generation Centrifugal – Here Today Environmental Responsibility Long Term Refrigerant Solution The industry’s n

Page 35 - Catalog WMC-4 35

40 Catalog WMC-4 Application Considerations Pumps To avoid the possibility of objectionable harmonics in the system piping, 4-pole, 1800/1500 rpm

Page 36 - 36 Catalog WMC-4

power and fan power must be examined. On the other hand, the low condenser water temperatures can be easy and economical to achieve in mild climates w

Page 37 - Catalog WMC-4 37

All interlock contacts must be rated for no less than 10 inductive amps. The alarm circuit provided in the control center utilizes 115-volts AC. The a

Page 38 - VFD Line Harmonics

43 Catalog WMC-4 The necessary procedure for reconnecting power from the generator back to the utility grid is shown below. These procedures are no

Page 39 - The IEEE 519-1991 Standard

44 Catalog WMC-4 Vessels Unit Marine water boxes Export packaging Can be either slat or full crate for additional protection during shipment. Unit

Page 40 - ! CAUTION

EMI filter NEMA 4 or NEMA 12 construction Factory-installed option. Radio interference filter. See page Ground Fault Protection 38 for details. Prote

Page 41 - Pumping

46 Catalog WMC-4 Refrigerant Recovery Units Although McQuay chillers can pump the entire refrigerant charge into the condenser and valve it off, th

Page 42 - ! WARNING

MODEL RRU570 Recovers at R-134a at 300 lb/min liquid and 5.7 lb/min vapor, ideal for the medium size chiller job. Rugged 3 hp open-drive compresso

Page 43 - Options and Accessories

SPECIFICATIONS Sensitivity: As low as 1 PPM Range: 0 to 1000 PPM Weight: 25 lbs. (11 kg) Size: W=16.5in. D=6.75in. H=15in. Power: 120/240 Volt, 50/6

Page 44 - Controls

Figure 28, Refrigerant Monitor Diagram Warranty Statement Limited Warranty Consult your local McQuay Representative for warranty details. Refer

Page 45 - Ground Fault Protection

Greater Reliability Exceptional Control Oil Handling Equipment Removed User-Friendly Touch Screen Panel With magnetic bearings operating in a magnetic

Page 46 - Refrigerant Recovery Units

Specifications SECTION 15XXX MAGNETIC BEARING CENTRIFUGAL CHILLERS PART 1 — GENERAL 1.1 SUMMARY Section includes design, performance criteria, refri

Page 47 - Refrigerant Monitors

1.7 MAINTENANCE A. Maintenance of the chillers shall be the responsibility of the owner. PART 2 — PRODUCTS 2.1 ACCEPTABLE MANUFACTURERS A. McQuay In

Page 48 - OPTIONS and ACCESSORIES

1. Evaporator and condenser shall be of the shell-and-tube type, designed, constructed, tested and stamped according to the requirements of the ASME

Page 49 - Warranty Statement

E. CHILLER CONTROL The unit shall have distributed microprocessor-based control architecture consisting of a 15-inch VGA touch-screen operator interfa

Page 50 - Specifications

The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit moni

Page 51 - Catalog WMC-4 51

B. Factory Start-Up Services: Provide for as long a time as is necessary to ensure proper operation of the unit, but in no case for less than two ful

Page 52 - 52 Catalog WMC-4

(800) 432-1342 • www.mcquay.com Catalog WMC-4 (08/07) This document contains the most current product information as

Page 53 - LONWORKS®

The Compressor Technology Variable Frequency Drives Compressor unloading and subsequent chiller capacity reduction is accomplished by a compressor-mou

Page 54 - LonTalk®)

Benefit Summary Highest Efficiency- in its size range; as low as .375 kW/ton. Smart refrigerant choice - The compressor is optimized for HFC-134a, the

Page 55 - Catalog WMC-4 55

8 Catalog WMC-4 Control Features The operator interface panel has a 15-inch Super VGA touch-screen, utilizing graphics to provide clear and concise

Page 56 - Catalog WMC-4 (08/07)

9 Catalog WMC-4 Figure 4, Control Panel The control system of the WMC chillers consists of two major components: the unit control panel, as shown t